Pre-insulated district-heating pipelines: Design and operational advice
T. Wonsyld,
R.F. Babus'Haq and
S.D. Probert
Applied Energy, 1992, vol. 42, issue 4, 227-236
Abstract:
Steady-state temperature distributions have been measured within a cylindrical duct enclosing two different diameter pipes--one for district heating and the other for the supply of domestic hot-water; the gaps between the pipes being filled with well-packed fibrous thermal insulant. The procedure was repeated successively with each of three sets of different-diameter pipes. The recommended configuration was with the DH pipe coaxial with the centre of the pipeline and the DHW one located vertically below it: this corresponded to the minimum rate of heat loss from the district-heating pipe under the considered conditions. An overall improvement of ~8% in the thermal insulation of the DH pipe has been achieved compared with the current conventional practice of installing the DHW pipe above the DH pipe.
Date: 1992
References: Add references at CitEc
Citations:
Downloads: (external link)
http://www.sciencedirect.com/science/article/pii/0306-2619(92)90014-3
Full text for ScienceDirect subscribers only
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:eee:appene:v:42:y:1992:i:4:p:227-236
Ordering information: This journal article can be ordered from
http://www.elsevier.com/wps/find/journaldescription.cws_home/405891/bibliographic
http://www.elsevier. ... 405891/bibliographic
Access Statistics for this article
Applied Energy is currently edited by J. Yan
More articles in Applied Energy from Elsevier
Bibliographic data for series maintained by Catherine Liu ().