Change in energy performance as a result of a R422D retrofit: An experimental analysis for a vapor compression refrigeration plant for a walk-in cooler
Ciro Aprea,
Angelo Maiorino and
Rita Mastrullo
Applied Energy, 2011, vol. 88, issue 12, 4742-4748
Abstract:
In this paper, the energy performance of a walk-in cooler working with R22 and its substitute R422D are experimentally studied. The experimental investigation was carried out considering three different operating conditions; in particular, the AHRI standard has been used as reference for operating conditions. All tests were run at steady state conditions and keeping the external air temperature at 35°C. The experimental analysis allowed the determination of cooling capacity, the electrical power absorbed, the COP and other variables characterizing the working of the plant. The results demonstrated that the cooling capacity for R422D was lower than for R22, while the electrical power absorbed with R422D was higher than that with R22. As consequence, the COP of R422D was lower than that of R22. Furthermore, technical proposals are introduced with the aim of improving the overall performances of those plants, which could be retrofitted with R422D.
Keywords: COP; Experimentation; R22; HFC; Retrofitting; R422D (search for similar items in EconPapers)
Date: 2011
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (4)
Downloads: (external link)
http://www.sciencedirect.com/science/article/pii/S0306261911004399
Full text for ScienceDirect subscribers only
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:eee:appene:v:88:y:2011:i:12:p:4742-4748
Ordering information: This journal article can be ordered from
http://www.elsevier.com/wps/find/journaldescription.cws_home/405891/bibliographic
http://www.elsevier. ... 405891/bibliographic
DOI: 10.1016/j.apenergy.2011.06.049
Access Statistics for this article
Applied Energy is currently edited by J. Yan
More articles in Applied Energy from Elsevier
Bibliographic data for series maintained by Catherine Liu ().