Diagnosis of the low temperature difference syndrome in the chilled water system of a super high-rise building: A case study
Dian-ce Gao,
Shengwei Wang,
Yongjun Sun and
Fu Xiao
Applied Energy, 2012, vol. 98, issue C, 597-606
Abstract:
The low delta-T syndrome exists in many large primary–secondary chilled water systems, which results in the degradation of the system overall energy performance. This paper presents a method and a case study on diagnosing the low delta-T problem resulted from the deficit flow that frequently occurred in the chilled water system of a super high-rise building at its early operation stage. The history operation data during the days when deficit flow and low delta-T syndrome occurred are analyzed. The improper set-point of outlet water temperature on the secondary side of heat exchangers is finally diagnosed as the fault that resulted in the deficit flow and low delta-T syndrome. Diagnosis of this fault was also validated in the in situ experimental tests. The deficit flow could be eliminated if temperature set-point was reset higher. Compared with the original set-point of outlet water temperature on the secondary side of heat exchangers, 87.67kW (72.37%) of the total power of pumps on primary and secondary sides of heat exchangers could be saved in the test cases when higher set-points were used.
Keywords: Chilled water system; Low delta-T syndrome; Deficit flow; Fault diagnosis (search for similar items in EconPapers)
Date: 2012
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (6)
Downloads: (external link)
http://www.sciencedirect.com/science/article/pii/S0306261912002772
Full text for ScienceDirect subscribers only
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:eee:appene:v:98:y:2012:i:c:p:597-606
Ordering information: This journal article can be ordered from
http://www.elsevier.com/wps/find/journaldescription.cws_home/405891/bibliographic
http://www.elsevier. ... 405891/bibliographic
DOI: 10.1016/j.apenergy.2012.03.057
Access Statistics for this article
Applied Energy is currently edited by J. Yan
More articles in Applied Energy from Elsevier
Bibliographic data for series maintained by Catherine Liu ().