A physical and semi-analytical comparison between coaxial BHE designs considering various piping materials
David Gordon,
Tirupati Bolisetti,
David S-K. Ting and
Stanley Reitsma
Energy, 2017, vol. 141, issue C, 1610-1621
Abstract:
This paper presents an improved semi-analytical model for the heat transfer related to a coaxial borehole heat exchanger (BHE). This model, referred to as the composite coaxial (CCx) model, is verified using results from three different thermal response tests performed on full-scale coaxial BHEs having various pipe size and material properties. The model is further used to analyze the performance and length requirements of various coaxial configurations comparing the use of a steel outer pipe to an insulated inner pipe. This comparison is made considering standard HDPE pipe sizes as the status quo, where the parameters are kept within the verified tested limit of the model. The results show, in comparison to using an insulated inner pipe, that a steel outer pipe has a greater impact on reducing the overall length requirement while maintaining system performance.
Keywords: Composite coaxial model; Borehole heat exchanger; Geothermal heat pump; Thermal response test; Coefficient of performance (search for similar items in EconPapers)
Date: 2017
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (7)
Downloads: (external link)
http://www.sciencedirect.com/science/article/pii/S0360544217318509
Full text for ScienceDirect subscribers only
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:eee:energy:v:141:y:2017:i:c:p:1610-1621