Energy savings of hybrid dew-point evaporative cooler and micro-channel separated heat pipe cooling systems for computer data centers
Yuting Liu,
Xu Yang,
Junming Li and
Xudong Zhao
Energy, 2018, vol. 163, issue C, 629-640
Abstract:
The world has entered the Age of Big Data with large data centers consuming large amounts of energy. 30%–50% of the energy delivered to a typical data center is consumed by the space cooling system. Dew-point evaporative coolers and heat pipes both utilizing natural cold resources can significantly reduce these refrigeration costs. This paper presents two hybrid cooling systems combining dew-point evaporative coolers with heat pipes for computing and data center cooling systems. The energy-saving potentials of two these hybrid cooling systems were analysed through calculations with comparisons with a traditional vapour compression refrigeration system. The results show that the average annual coefficients of performance (COP) of the ideal hybrid refrigeration systems are 33 and 34 which leads to annual energy savings of nearly 90% compared with vapour compression refrigeration.
Keywords: Hybrid cooling system; Micro-channel separated heat pipe; Dew-point evaporative cooler; CDCs (search for similar items in EconPapers)
Date: 2018
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (20)
Downloads: (external link)
http://www.sciencedirect.com/science/article/pii/S0360544218314695
Full text for ScienceDirect subscribers only
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:eee:energy:v:163:y:2018:i:c:p:629-640
DOI: 10.1016/j.energy.2018.07.172
Access Statistics for this article
Energy is currently edited by Henrik Lund and Mark J. Kaiser
More articles in Energy from Elsevier
Bibliographic data for series maintained by Catherine Liu ().