EconPapers    
Economics at your fingertips  
 

Temperature stratification in hot-water storage tanks

K. Hariharan, K. Badrinarayana, S. Srinivasa Murthy and M.V. Krishna Murthy

Energy, 1991, vol. 16, issue 7, 977-982

Abstract: Experiments have been carried out on a scale model of stratified hot-water storage tanks to study the effects of operating conditions on the thermoclines and on the extraction efficiency. The following parameters were varied: the cold-water temperature (from 30 to 80 °C), hot-water temperature (from 40 to 90 °C), water-flow rate (from 6 to 601/h), and LD ratio (1.56, 2.06, 3.54 and 4.0). Care was taken to keep the total volume and dD ratio the same for all tanks. It was observed that stratification improves with increasing ΔT and water flow rates. LD values between 3 and 4 are optimal. The extraction efficiency has been correlated by an analytical expression.

Date: 1991
References: View complete reference list from CitEc
Citations: View citations in EconPapers (6)

Downloads: (external link)
http://www.sciencedirect.com/science/article/pii/036054429190057S
Full text for ScienceDirect subscribers only

Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.

Export reference: BibTeX RIS (EndNote, ProCite, RefMan) HTML/Text

Persistent link: https://EconPapers.repec.org/RePEc:eee:energy:v:16:y:1991:i:7:p:977-982

DOI: 10.1016/0360-5442(91)90057-S

Access Statistics for this article

Energy is currently edited by Henrik Lund and Mark J. Kaiser

More articles in Energy from Elsevier
Bibliographic data for series maintained by Catherine Liu ().

 
Page updated 2025-03-19
Handle: RePEc:eee:energy:v:16:y:1991:i:7:p:977-982