An air-conditioning unit with a zeotropic mixture controlled by a distillation column
Yang Zhao,
Ma Yitai,
Zhao Sanyuan and
Li Yie
Energy, 1998, vol. 23, issue 9, 777-784
Abstract:
We describe a new air-conditioning and heat-pump system, which may be used to separate a refrigerant mixture efficiently and adjust the composition in the system with cooling- or heating-load changes. A dynamic model has been developed to analyze the transient behavior of the capacity-control system. An air conditioner equipped with a small distillation circuit has been tested. Increases in the SEERs (seasonal energy efficiency ratios) for the new composition-controlled system are 28.3 and 17.7% and capacity changes 57.3–91.8% and 71.5–101%, respectively, for R22/142b and R23/124.
Date: 1998
References: View complete reference list from CitEc
Citations: View citations in EconPapers (1)
Downloads: (external link)
http://www.sciencedirect.com/science/article/pii/S0360544297001114
Full text for ScienceDirect subscribers only
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:eee:energy:v:23:y:1998:i:9:p:777-784
DOI: 10.1016/S0360-5442(97)00111-4
Access Statistics for this article
Energy is currently edited by Henrik Lund and Mark J. Kaiser
More articles in Energy from Elsevier
Bibliographic data for series maintained by Catherine Liu ().