EconPapers    
Economics at your fingertips  
 

Building energy model calibration with schedules derived from electricity use data

Yang-Seon Kim, Mohammad Heidarinejad, Matthew Dahlhausen and Jelena Srebric

Applied Energy, 2017, vol. 190, issue C, 997-1007

Abstract: Building energy models can accurately predict energy performance of buildings, if properly calibrated. This study developed and demonstrated a novel method to calibrate building energy models based on the occupancy and plug-load schedules derived from metered electric use data. Importantly, this study also proposed an occupancy assessment method applicable to resource limited situation when a building sub-metering system is not available. Furthermore, the developed method can facilitate accurate predictions of building energy performance without a requirement to simultaneously monitor energy use and occupancy rates. The method development process used data from an office type building (OB1), and further verified the method accuracy with data from two campus buildings (CB1 and CB2). The developed method is novel because it considers interactions of the validated modeled occupancy patterns, processed electricity use patterns, and the calibrated building energy model results at the hourly level. This approach allows addressing limitations in the current studies that are not fully capable of modeling occupancy patterns, electricity use patterns, and calibrated building energy models with this level of granularity. The accuracy of the building energy modeling results increases with the derived occupancy schedules and plug-loads. Specifically, the Coefficient of Variation Root Mean Square Error (CVRMSE) of OB1 building energy modeling results improved from 21% to 12% compared to the modeling results obtained with default schedules. The results from case study buildings CB1 and CB2 show that the accuracy of modeling results increased as the hourly electricity CVRMSE decreased from 128% to 31% and from 156% to 16%, respectively. These improvements are significant, while the developed method is applicable to other office or campus buildings from the category of medium-size commercial buildings. Finally, the identification of actual occupancy rates provides opportunities for inexpensive implementation of occupant-based controllers in buildings.

Keywords: Building energy modeling; Building energy calibration; Commercial buildings; Occupants in building; Building energy simulation (search for similar items in EconPapers)
Date: 2017
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (15)

Downloads: (external link)
http://www.sciencedirect.com/science/article/pii/S0306261916319481
Full text for ScienceDirect subscribers only

Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.

Export reference: BibTeX RIS (EndNote, ProCite, RefMan) HTML/Text

Persistent link: https://EconPapers.repec.org/RePEc:eee:appene:v:190:y:2017:i:c:p:997-1007

Ordering information: This journal article can be ordered from
http://www.elsevier.com/wps/find/journaldescription.cws_home/405891/bibliographic
http://www.elsevier. ... 405891/bibliographic

DOI: 10.1016/j.apenergy.2016.12.167

Access Statistics for this article

Applied Energy is currently edited by J. Yan

More articles in Applied Energy from Elsevier
Bibliographic data for series maintained by Catherine Liu ().

 
Page updated 2025-03-19