Techno-economic analysis of hybrid ACC performance under different meteorological conditions

Jacques du Plessis and Michael Owen

Energy, 2022, vol. 255, issue C

Abstract: A hybrid air-cooled condenser (ACC) concept has demonstrated to provide performance benefits over a conventional ACC. Additional to the thermal performance, the cost effectiveness should also be considered to determine the commercial viability, and therefore this study interrogates the techno-economic feasibility of a hybrid ACC at six locations with a ∼238 MW steam turbine representative of a typical CSP or NGCC plant. In this paper the hybrid ACC, is compared to a conventional ACC in terms of annual performance and annualized cost. The annualized cost of the hybrid ACC relative to the conventional ACC is expressed as a cost ratio φₐ, and consideration is given to a range of water and hybrid unit capital costs.

Keywords: Hybrid cooling; Power generation; Air-cooled condenser; Annual performance; Energy system (search for similar items in EconPapers)
Date: 2022
References: View complete reference list from CitEc
Citations:

Downloads: (external link)
http://www.sciencedirect.com/science/article/pii/S0360544222013974
Full text for ScienceDirect subscribers only

Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.

Export reference: BibTeX RIS (EndNote, ProCite, RefMan) HTML/Text

Persistent link: https://EconPapers.repec.org/RePEc:eee:energy:v:255:y:2022:i:c:s0360544222013974

DOI: 10.1016/j.energy.2022.124494

Access Statistics for this article

Energy is currently edited by Henrik Lund and Mark J. Kaiser

More articles in Energy from Elsevier
Bibliographic data for series maintained by Catherine Liu ().

 
Page updated 2025-03-19
Handle: RePEc:eee:energy:v:255:y:2022:i:c:s0360544222013974