Challenges and potentials of using a local heat pump in a 5 GDHC solution: Results from field and laboratory evaluations
Jonas Lindhe,
Martin Larsson,
Morgan Willis,
Pia Tiljander and
Dennis Johansson
Energy, 2024, vol. 289, issue C
Abstract:
In fifth generation district heating and cooling (5GDHC), the temperature range of the heat source is wider then in current common heat pump systems. The results of this study show that the heat pumps and chillers that are available in the market are not well adapted to 5GDHC applications due to the wide working range of 5GHDC. In order to maintain a high efficiency, current design parameters should be adjusted. This affects the dimensioning of all components in the refrigerant circuit and the required volume of refrigerant.
Date: 2024
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (1)
Downloads: (external link)
http://www.sciencedirect.com/science/article/pii/S0360544223032012
Full text for ScienceDirect subscribers only
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:eee:energy:v:289:y:2024:i:c:s0360544223032012
DOI: 10.1016/j.energy.2023.129807
Access Statistics for this article
Energy is currently edited by Henrik Lund and Mark J. Kaiser
More articles in Energy from Elsevier
Bibliographic data for series maintained by Catherine Liu ().